I/O module - AXL F DO16 FLK 1H - 2701813

Produttore:
PHOENIX CONTACT
Phoenix%20contact

74e4634234e45d53592227396ed32854f9f55e53 medium
Prezzo (IVA esclusa)
€ 185.00
Codice Nuova Elva
2701813
Codice produttore
2701813
Disponibilità
Invia RdO

Axioline F, Digital output module, Digital outputs: 16, 24 V DC, 500 mA, connection method: FLK connector (20-pos.), transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connector

Features

  • 16 digital outputs

  • 24 V DC, 500 mA

  • 1 FLK connection, 20-pos.

  • Minimum update time of < 100 μs

  • Device rating plate stored

  • Diagnostic and status indicators

  • BV

  • BSH

  • cULus Listed

  • LR

  • RINA

  • PRS

  • NK

  • DNV GL

  • KR

  • ABS

  • UL Listed

  • cUL Listed

Specifications

Depth54 mm
Height126.1 mm
Output Voltage24 V
Strip Length8 mm
Width35 mm

Electrical isolation

Test section5 V supply of the local bus (UBus) / 24 V supply (I/Os) 500 V AC 50 Hz 1 min.
Test section5 V supply of the local bus (UBus) / functional ground 500 V AC 50 Hz 1 min.
Test section24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min.

Standards and Regulations

Mechanical testsVibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
Mechanical testsShock in acc. with EN 60068-2-27/IEC 60068-2-27 30g, 11 ms period, half-sine shock pulse
Mechanical testsContinuous shock according to EN 60068-2-27/IEC 60068-2-27 10g
Protection classIII (IEC 61140, EN 61140, VDE 0140-1)

Environmental Product Compliance

REACh SVHCLead 7439-92-1
China RoHSEnvironmentally Friendly Use Period = 50 years
China RoHSFor details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

Axioline potentials

DesignationAxioline F local bus supply (UBus)
Supply voltage5 V DC (via bus base module)
Current consumptionmax. 120 mA
Power consumptionmax. 600 mW
DesignationSupply for digital output modules (UO)
Supply voltage24 V DC
Supply voltage range19.2 V DC - 30 V DC (including all tolerances, including ripple)
Current consumptionmax. 8 A (provide external protection)
Power consumptionmax. 240 W (of which 560 mW with internal losses)
Protective circuitSurge protection of the supply voltage electronic (35 V, 0.5 s)
Protective circuitPolarity reversal protection of the supply voltage parallel diode; with external 5 A fuse (only for commissioning)
Protectionmax. 8 A (polarity reversal protection up to 5 A)

Connection data

DesignationAxioline F connector
Connection methodPush-in connection
Note on the connection methodPlease observe the information provided on conductor cross sections in the 'Axioline F: system and installation' user manual.
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.1.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.1.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.16
Stripping length8 mm

Dimensions

Width35 mm
Height126.1 mm
Depth54 mm
Note on dimensionsThe depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715).

Interfaces

DesignationAxioline F local bus
No. of channels2
Connection methodBus base module
Transmission speed100 Mbps

Digital outputs

Output nameDigital outputs
Connection methodFLK20 pin strip
Connection technologyFLK connector (20-pos.)
Number of outputs16
Protective circuitShort-circuit protection, overload protection of the outputs Electronic
Output voltage24 V
Nominal output voltage24 V DC
Maximum output current per channel500 mA
Maximum output current per module8 A (provide external protection)
Nominal load, inductivemax. 12 VA (1.2 H, 48 Ω, with nominal voltage)
Nominal load, lampmax. 12 W (at nominal voltage)
Nominal load, ohmicmax. 12 W (48 Ω, with nominal voltage)
Switching frequencymax. 10000 per second (with at least 50 mA load current)
Load min.10 kΩ
Output voltage when switched offmax. 1 V
Output current when switched offmax. 300 µA
Behavior with overloadShutdown with automatic restart
Behavior with inductive overloadOutput can be destroyed
Reverse voltage resistance to short pulseslimited protection up to 0.5 A for 1 s

Ambient conditions

Permissible humidity (storage/transport)5 % - 95 % (non-condensing)
Air pressure (operation)70 kPa - 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa - 106 kPa (up to 3000 m above sea level)
Degree of protectionIP20
Ambient temperature (operation)-25 °C - 60 °C
Ambient temperature (storage/transport)-40 °C - 85 °C
Permissible humidity (operation)5 % - 95 % (non-condensing)

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Spesso acquistati assieme


Altri articoli da PHOENIX CONTACT

Richiedi un preventivo