IEC contactor, TeSys Deca, nonreversing, 80A, 60HP at 480VAC, 3 phase, 3 pole, 3 NO, 24VAC 50/60Hz coil, open style

Manufactured by:
Schneider Electric
Schneider electric

8e834675d1543cf97e1090cd22d9de96b0fcea22 medium
Price (VAT excluded)
€ 353.25
Nuova Elva code
LC1D80AB7
Manufacturer code
LC1D80AB7
Availability
1 in stock

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 80A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. Contactor is supplied with a 24 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.90 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.

Specifications

CertificationsCCC
Contact Configuration1 NO + 1 NC
Depth120 mm
Height122 mm
Impedance1.5 MOhm - Ith 80 A 50 Hz Power Circuit
Net Weight0.86 kg
StandardCSA C22.2 No 60947-4-1
Warranty Length18 months
Width55 mm

Specifications

[Uc] Control Circuit Voltage24 V AC 50/60 Hz
Device Short NameLC1D
[Ue] Rated Operational Voltagepower circuit 690 V AC 25...400 Hz || power circuit 300 V DC
Range Of ProductTeSys Deca
Contactor Applicationmotor control || resistive load
Product Or Component Typecontactor
RangeTeSys || TeSys Deca
Utilisation CategoryAC-1 || AC-4 || AC-3 || AC-3e
[Ie] Rated Operational Current80 A 60 °C) <= 440 V AC-1 power circuit || 66 A 60 °C) <= 440 V AC-3 power circuit || 66 A 60 °C) <= 440 V AC-3e power circuit
Poles Description3P

Contractual warranty

Warranty18 months

Complementary

Non-Overlap Time1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Control Circuit TypeAC 50/60 Hz standard
Safety Reliability LevelB10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Pollution Degree3
Insulation Resistance> 10 MOhm signalling circuit
Rated Breaking Capacity1000 A 440 V power circuit IEC 60947
Irms Rated Making Capacity140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 1000 A 440 V AC power circuit IEC 60947
Associated Fuse Rating10 A gG signalling circuit IEC 60947-5-1 || 125 A gG <= 690 V type 1 power circuit || 125 A gG <= 690 V type 2 power circuit
[Uimp] Rated Impulse Withstand Voltage6 kV IEC 60947
Inrush Power In Va140-140 VA 60 Hz 0.75 20 °C) || 160-160 VA 50 Hz 0.75 20 °C)
Pole Contact Composition3 NO
Minimum Switching Current5 mA signalling circuit
Connections - Terminalscontrol circuit screw clamp terminals 2 1-2.5 mm² flexible with cable end || control circuit screw clamp terminals 1 1-4 mm² flexible with cable end || power circuit EverLink BTR screw connectors 1 1-35 mm² flexible with cable end || power circuit EverLink BTR screw connectors 2 1-25 mm² flexible with cable end || control circuit screw clamp terminals 1 1-4 mm² solid || control circuit screw clamp terminals 2 1-4 mm² solid || power circuit EverLink BTR screw connectors 1 1-35 mm² solid || power circuit EverLink BTR screw connectors 2 1-25 mm² solid || control circuit screw clamp terminals 1 1-4 mm² flexible || control circuit screw clamp terminals 2 1-4 mm² flexible || power circuit EverLink BTR screw connectors 1 1-35 mm² flexible || power circuit EverLink BTR screw connectors 2 1-25 mm² flexible
Coil Technologywithout built-in suppressor module
Operating Time4...19 ms opening || 12...26 ms closing
Minimum Switching Voltage17 V signalling circuit
Maximum Operating Rate3600 cyc/h 60 °C
Signalling Circuit Frequency25...400 Hz
Tightening Torquecontrol circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connectors 1-25 mm² hexagonal 4 mm || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2
Electrical Durability0.7 Mcycles 80 A AC-1 <= 440 V || 1 Mcycles 66 A AC-3 <= 440 V || 1 Mcycles 66 A AC-3e <= 440 V
Mechanical Durability6 Mcycles
Auxiliary Contacts Typemechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Power Dissipation Per Pole9.6 W AC-1 || 6.5 W AC-3 || 6.5 W AC-3e
Compatibility CodeLC1D
Hold-In Power Consumption In Va13-13 VA 60 Hz 0.3 20 °C) || 15-15 VA 50 Hz 0.3 20 °C)
Overvoltage CategoryIII
Maximum Horse Power Rating5 hp 115 V at AC 60 Hz for 1 phase || 10 hp 230/240 V at AC 60 Hz for 1 phase || 20 hp 200/208 V at AC 60 Hz for 3 phase || 20 hp 230/240 V at AC 60 Hz for 3 phase || 40 hp 460/480 V at AC 60 Hz for 3 phase || 50 hp 575/600 V at AC 60 Hz for 3 phase
Motor Power Kw18.5 kW 220...230 V AC 50 Hz AC-3) || 37 kW 380...400 V AC 50 Hz AC-3) || 37 kW 415 V AC 50 Hz AC-3) || 37 kW 440 V AC 50 Hz AC-3) || 37 kW 500 V AC 50 Hz AC-3) || 37 kW 660...690 V AC 50 Hz AC-3)
[Ui] Rated Insulation Voltagesignalling circuit 690 V IEC 60947-1 || power circuit 690 V IEC 60947-4-1
[Icw] Rated Short-Time Withstand Current520 A 40 °C - 10 s power circuit || 900 A 40 °C - 1 s power circuit || 110 A 40 °C - 10 min power circuit || 260 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
Heat Dissipation4-5 W 50/60 Hz
Protective Coverwith
Average Impedance1.5 mOhm - Ith 80 A 50 Hz power circuit
Auxiliary Contact Composition1 NO + 1 NC
[Ith] Conventional Free Air Thermal Current10 A 60 °C signalling circuit || 80 A 60 °C power circuit
Control Circuit Voltage Limits0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz
Mounting Supportplate || rail
Contact CompatibilityM2

Offer Sustainability

Rohs Exemption InformationYes
China Rohs RegulationPro-active China RoHS declaration (out of China RoHS legal scope)
Eu Rohs DirectiveCompliant
Mercury FreeYes
Environmental DisclosureENVPEP110205EN
Sustainable Offer StatusGreen Premium product
Pvc FreeYes
Toxic Heavy Metal FreeYes
Reach RegulationFree of Substances of Very High Concern above the threshold
Reach Free Of SvhcYes
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.

Environment

Product CertificationsCCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping)
Operating Altitude0...9842.52 ft (0...3000 m)
Fire Resistance850 °C IEC 60695-2-1
Width55 mm
Depth120 mm
Permissible Ambient Air Temperature Around The Device-40-60 °C || 60-70 °C with derating
Height122 mm
StandardsEN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC 60335-1
Climatic WithstandIACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Net Weight0.86 kg
Flame RetardanceV1 conforming to UL 94
Protective TreatmentTHIEC 60068-2-30
Ip Degree Of ProtectionIP20 front face IEC 60529
Mechanical Robustnessvibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 10 Gn for 11 ms)