TeSys Mini-Vario - emergency stop switch disconnector - 12 A - on door

Produttore:
Schneider Electric
Schneider%20electric

8b939be46592aef4e1db1fe79640d6e2793ec344 medium
Prezzo (IVA esclusa)
€ 19.89
Codice Nuova Elva
VCDN12
Codice produttore
VCDN12
Disponibilità
Tempo di consegna standard: 7 giorni

VCDN12 is a 3-pole TeSys Vario switch-disconnector from Schneider Electric for emergency stop switching in motor applications 4kW@400V AC-23. For enclosure door mounting, it provides a red & yellow operator/yellow plate with IP65 protection. VCDN12 is a 3-pole TeSys Vario switch-disconnector from Schneider Electric for main and emergency stop switching in motor applications 4kW@400V AC-23. It consists of a VZ12 Vario switch body and a padlockable red & yellow operator to be mounted on door with a single fixing. It ensures an IP65 protection to the mounting. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach). Vario 3-pole rotary switch disconnector for door mounting. Composed with a switch body VZ12 and a red & yellow operator, for emergency stop, padlockable. Ensures an IP65 protection to the mounting. Rated for 690V AC operation, DC operation is permitted until 250V, performance depending on the number of contacts in series. Possible attachment of 2 add-on poles (1 in each side) , main (VZN12), neutral (VZN11), earthing (VZN14), auxiliary (VZN05, VZN06).

Specifications

CertificationsCCC
Height60 mm
Net Weight0.177 kg
StandardIEC 60947-3
Warranty Length18 months
Width60 mm

Specifications

Rotary Handle Padlocking1 to 3 padlocks 4-8 mm
Control Typerotary handle
Contacts Type And Composition3 NO
Poles Description3P
Device Short NameVCDN
Rotary Handle Mounting Styledirect
Network TypeAC || DC
Handle Front Plate Colouryellow
Handle Colourred
Product Or Component Typeemergency stop switch disconnector
Product NameTeSys Mini-VARIO
Performance Levelstandard
RangeTeSys

Contractual warranty

Warranty18 months

Complementary

[Ue] Rated Operational Voltage690 V AC 50/60 Hz
[Uimp] Rated Impulse Withstand Voltage6 kV
Making Capacity120 A 400 V AC-21A || 120 A 400 V AC-22A || 120 A 400 V AC-23A
Connections - Terminalspower circuit screw clamp terminals 4-4 mm² flexible - with cable end || power circuit screw clamp terminals 4-4 mm² solid
[Icm] Rated Short-Circuit Making Capacity0.5 kA 400 V at Ipeak
Electrical Durability30000 cycles DC-1...5 || 50000 cycles AC-21
Suitability For Isolationyes
Mounting Supporthandle door || switch door
[Ie] Rated Operational Current8.1 A AC-23)400 V
Mechanical Durability50000 cycles
Width60 mm
Height60 mm
Tightening Torquepower circuit 0.7-0.7 N.m screw clamp terminals
Device Compositionhandle || switch
Breaking Capacity120 kA 400 V AC-21A) || 120 kA 400 V AC-22A) || 120 kA 400 V AC-23A)
Rated Operational Power In W3 kW 230...240 V AC-23A) || 4 kW 400...415 V AC-23A) || 5.5 kW 500 V AC-23A) || 7.5 kW 690 V AC-23A) || 1.5 kW 230...240 V AC-3) || 3 kW 400...415 V AC-3) || 4 kW 500 V AC-3) || 4 kW 690 V AC-3)
Rated Conditional Short-Circuit Current6 kA 400 V 12 A aM || 6 kA 400 V 12 A gG
[Icw] Rated Short-Time Withstand Current140 A 400 V 1 s
Intermittent Duty Class30
[Ith] Conventional Free Air Thermal Current12 A
Fixing Modehole 22.5 mm handle
[Ithe] Conventional Enclosed Thermal Current10 A
Marking0 - 1
Base Dimension60 x 60 mm
Net Weight0.177 kg

Offer Sustainability

Rohs Exemption InformationYes
Eu Rohs DirectiveCompliant
Mercury FreeYes
Environmental DisclosureENVPEP110227EN
Sustainable Offer StatusGreen Premium product
Pvc FreeYes
Reach RegulationReference contains Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs RegulationProduct out of China RoHS scope. Substance declaration for your information.

Environment

Product CertificationsGL || CCC || UL || CSA || UKCA
Ambient Air Temperature For Operation-20-50 °C
StandardsIEC 60947-3
Ip Degree Of ProtectionIP65
Protective TreatmentTC
Mechanical Robustnessvibrations 10...150 Hz 5 gn) IEC 60068-2-6 || shocks 11 ms 15 gn) IEC 60068-2-27
Fire Resistance960 °C IEC 60695-2-1