Modular timing relay, Harmony, 8A, 1CO, 1s..100h, asymmetrical flashing, 24V DC 24...240V AC DC

Produttore:
Schneider Electric
Schneider%20electric

Fda55be6964fa4c0e73f020a319d4d447ec5e8e6 medium
Prezzo (IVA esclusa)
€ 76.96
Codice Nuova Elva
RE17RLMU
Codice produttore
RE17RLMU
Disponibilità
Invia RdO

This Harmony RE17R timing relay can be set between 0.1 seconds and 100 hours, has an output rating of 8A, is 17.5mm wide and can be supplied with 24V DC, 24V to 240V AC. It also has 1 changeover contact SPDT (single pole double throw). It has one of market slimmest form-factors, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 1-pole DIN device. It also offers a sealable cover, simple and precise settings with rotary trimmers. Single function timer for a simple integration in hard-wired logic schematics, ideal for refurbishment of old installations without using a PLC. 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Specifications

CertificationsCSA
Depth72 mm
Height90 mm
Input Voltage10 V
Net Weight0.07 kg
Standard2004/108/EC
Storage Temperature-30-60 °C
Width17.5 mm

Specifications

Discrete Output Typerelay
Range Of ProductHarmony Timer Relays
Product Or Component Typedual function relay
Time Delay Range1...10 h || 1...10 s || 0.1...1 s || 6...60 min || 1...10 min || 10...100 h || 6...60 s
Nominal Output Current8 A
Width17.5 mm
Time Delay Typeasymmetrical flashing
Device Short NameRE17R

Complementary

Safety Reliability DataMTTFd = 296.8 years || B10d = 270000
Contacts Materialcadmium free
Power Consumption In Va0-32 VA 240 V AC
Dielectric Strength2.5 kV 1 mA/1 minute 50 Hz IEC 61812-1
MarkingCE
Voltage Range0.85...1.1 Us
Reset Time120 ms on de-energisation typical
Operating Rate In Hz10 Hz
Net Weight0.07 kg
Mounting Positionany position in relation to normal vertical mounting plane
Voltage Drift+/- 0.2 %/V
Setting Accuracy Of Time Delay+/- 10 % of full scale 25 °C IEC 61812-1
Maximum Switching Voltage250 V AC
Connections - Terminalsscrew terminals, 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
Functionalityasymmetrical flashing timer
Contacts Type And Composition1 C/O
[Us] Rated Supply Voltage24...240 V AC 50/60 Hz || 24 V DC
Temperature Drift+/- 0.05 %/°C
Local SignallingLED indicator on steady: relay energised, no timing in progress || LED indicator 80 % ON and 20 % OFF flashing: timing in progress
Minimum Switching Current10 mA 5 V DC
Input Voltage10 V
Mounting Support35 mm DIN rail conforming to EN/IEC 60715
Height90 mm
Electrical Durability100000 cycles resistive 8 A 250 V AC
Mechanical Durability10000000 cycles
Compatibility CodeRE17
Breaking Capacity2000 VA
On-Load Factor100 %
Housing Materialself-extinguishing
Impulse Duration100 ms with load in parallel typical || 30 ms typical
Time Delay TypeL, Li
[Uimp] Rated Impulse Withstand Voltage5 kV 1.2/50 µs
Depth72 mm
Creepage Distance4 kV/3 IEC 60664-1
Tightening Torque0.6-1 N.m IEC 60947-1
Supply Frequency50...60 Hz +/- 5 %
Repeat Accuracy+/- 0.5 % IEC 61812-1
Maximum Delay Response100 ms
Control Typeselector switch front panel
Insulation Resistance100 MOhm 500 V DC IEC 60664-1
Maximum Power Consumption In W0.6 W 24 V DC
Maximum Switching Current8 A AC/DC

Offer Sustainability

Rohs Exemption InformationYes
Mercury FreeYes
Environmental DisclosureENVPEP121117EN
Sustainable Offer StatusGreen Premium product
Reach RegulationReference contains Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
China Rohs RegulationX
Circularity ProfileENVEOLI121113EN
Eu Rohs DirectivePro-active compliance (Product out of EU RoHS legal scope)

Environment

Product CertificationsGL || cULus || CSA
Relative Humidity93-93 % without condensation IEC 60068-2-30
Ambient Air Temperature For Operation-20-60 °C
Standards2006/95/EC || EN 61000-6-2 || EN 61000-6-4 || 2004/108/EC || IEC 61812-1 || EN 61000-6-3 || EN 61000-6-1
Immunity To Microbreaks20 ms
Electromagnetic Compatibilityelectrostatic discharge immunity test 6 kV in contact) level 3 IEC 61000-4-2 || electrostatic discharge immunity test 8 kV in air) level 3 IEC 61000-4-2 || susceptibility to electromagnetic fields 10 V/m 80 MHz to 1 GHz) level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test 1 kV capacitive connecting clip) level 3 IEC 61000-4-4 || electrical fast transient/burst immunity test 2 kV direct) level 3 IEC 61000-4-4 || 1.2/50 µs shock waves immunity test 1 kV differential mode) level 3 IEC 61000-4-5 || 1.2/50 µs shock waves immunity test 2 kV common mode) level 3 IEC 61000-4-5 || conducted RF disturbances 10 V 0.15...80 MHz) level 3 IEC 61000-4-6 || voltage dips and interruptions immunity test 0 % 1 cycle) IEC 61000-4-11 || voltage dips and interruptions immunity test 70 % 25/30 cycles) IEC 61000-4-11 || conducted and radiated emissionsclass B EN 55022
Shock Resistance15 gn 11 ms IEC 60068-2-27
Vibration Resistance20 m/s² 10-150 Hz)IEC 60068-2-6
Ip Degree Of ProtectionIP20 IEC 60529 terminal block) || IP40 IEC 60529 housing) || IP50 IEC 60529 front panel)
Ambient Air Temperature For Storage-30-60 °C

Documentazione


Spesso acquistati assieme


Altri articoli da Schneider Electric

Richiedi un preventivo