Miniature circuit breaker (MCB), Multi9 C60N, 2P, 6A, C curve, 10kA (IEC/EN 60947-2)

Produttore:
Schneider Electric
Schneider%20electric

067666b1454cddeca54d42df0ea8391b139e2dde medium
Codice Nuova Elva
M9F11206
Codice produttore
M9F11206
Disponibilità
Invia RdO

This Multi9 C60N is a low voltage miniature circuit breaker (MCB). It is a 2P circuit breaker with 2 protected poles, 6A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 10kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. Its fast closing mechanism, overvolatge resistance and high performance limitation improve its service life. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The operating frequency is 50Hz or 60Hz. The product can be clipped on a DIN rail. Its width is 4 pitches of 9mm. Pollution degree is 3. Overvoltage category is IV. The product colour is light grey (RAL7035). The dimensions are (W) 36mm x (H) 81mm x (D) 72mm. The weight is 0.24kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.

Specifications

CertificationsCCC
ColorGray
Depth72 mm
Height81 mm
Line Rated Current50 °C
Mounting TypeClip-On
Net Weight0.24 kg
StandardEN/IEC 60947-2
Storage Temperature-40-80 °C
Strip Length14 mm
Width36 mm

Specifications

Line Rated Current6 A 50 °C EN/IEC 60947-2
RangeMulti9
Breaking Capacity20 kA Icu <= 125 V DC EN/IEC 60947-2 || 10 kA Icu 415 V AC 50/60 Hz between phases EN/IEC 60947-2 || 20 kA Icu 240 V AC 50/60 Hz between phases EN/IEC 60947-2 || 6 kA Icu 440 V AC 50/60 Hz between phases EN/IEC 60947-2
Suitability For Isolationyes EN/IEC 60947-2
Poles Description2P
Device Applicationdistribution
Device Short NameC60N
Trip Unit Technologythermal-magnetic
Curve CodeC
Number Of Protected Poles2
Network TypeAC || DC
StandardsEN/IEC 60947-2
Product CertificationsEAC || KC || CCC
Product Or Component Typeminiature circuit-breaker
Product NameMulti9 C60
Utilisation Categorycategory A EN/IEC 60947-2

Complementary

Network Frequency50/60 Hz
Wire Stripping Length14 mm top or bottom
Control Typetoggle
Connections - Terminalstunnel type terminal top or bottom) 1-25 mm² - rigid || tunnel type terminal top or bottom) 1-25 mm² - flexible || tunnel type terminal top or bottom) 1-25 mm² - flexible with ferrule
[Ui] Rated Insulation Voltage500 V AC 50/60 Hz EN/IEC 60947-2
Mounting Modeclip-on
Electrical Durability10000 cycles
Mechanical Durability20000 cycles
Local SignallingON/OFF indication
[Uimp] Rated Impulse Withstand Voltage6 kVEN/IEC 60947-2
ColorGray
[Ics] Rated Service Breaking Capacity7.5 kA 75 % EN/IEC 60947-2 - 415 V AC 50/60 Hz || 16 kA 75 % EN/IEC 60947-2 - 240 V AC 50/60 Hz || 4.5 kA 75 % EN/IEC 60947-2 - 440 V AC 50/60 Hz || 20 kA 100 % EN/IEC 60947-2 - <= 125 V DC
Width36 mm
Provision For Padlockingpadlockable
Depth72 mm
Tightening Torque2-2 N.m top or bottom
Magnetic Tripping Limit8.5 x In +/- 20 % AC || 12 x In +/- 20 % DC
[Ue] Rated Operational Voltage240 V AC 50/60 Hz between phases || 415 V AC 50/60 Hz between phases || 440 V AC 50/60 Hz between phases || <= 125 V DC
Height81 mm
Contact Position Indicatoryes
Earth-Leakage Protectionseparate block
Mounting SupportDIN rail
9 Mm Pitches4
Limitation Class3
Net Weight0.24 kg

Offer Sustainability

Rohs Exemption InformationYes
Mercury FreeYes
Environmental DisclosureENVPEP1304004
Sustainable Offer StatusGreen Premium product
Reach RegulationReference contains Substances of Very High Concern above the threshold
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs RegulationProduct out of China RoHS scope. Substance declaration for your information.
Eu Rohs DirectiveCompliant
Halogen Content PerformanceHalogen free product

Environment

Ambient Air Temperature For Operation-30-70 °C
Tropicalisation2 IEC 60068-1
Ip Degree Of ProtectionIP20 conforming to IEC 60529 || IP40 (modular enclosure) conforming to IEC 60529
Pollution Degree3 EN/IEC 60947-2
Ambient Air Temperature For Storage-40-80 °C
Relative Humidity95-95 % 55-55 °C
Overvoltage CategoryIV
Heat Dissipation5.4-5.4 W 415 V - 6 A

Documentazione


Altri articoli da Schneider Electric

Richiedi un preventivo