Electronic time delay auxiliary contact block, TeSys K, 1C/O, on delay 1-30s, front, control 110...240V AC

Produttore:
Schneider Electric
Schneider%20electric

32e4ce1d6cbfc1f39c039ac2d707f8deb8c6ef7c medium
Prezzo (IVA esclusa)
€ 58.36
Codice Nuova Elva
LA2KT2U
Codice produttore
LA2KT2U
Disponibilità
Invia RdO

TeSys K electronic time delay contact block, for contactors LC.K, LP.K, CA.K. It provides 1C/O contact rated up to 2A 240V AC, with an on-delay setting range 1-30s. To be used for contactors with 110-240V AC/DC coils (F7 to U7, FD to UD). Front mounting by clip-on, connections by attached wires to the contactor. It conforms to RoHS/REACh regulation.

Specifications

CertificationsCE
Contact Configuration1 C/O
Depth38 mm
Height27 mm
Net Weight0.04 kg
StandardCSA C22.2 No 60947-5-1
Warranty Length18 months
Width38 mm

Specifications

Product CertificationsUL || CSA || CE || UKCA
RangeTeSys
Mounting Locationfront
Pole Contact Composition1 C/O
Time Delay Range1...30 s
Auxiliary Contacts Operationtime delay
Device Short NameLA1
[Ith] Conventional Free Air Thermal Current2 A signalling circuit
StandardsEN/IEC 60947-5-1 || UL 60947-5-1 || CSA C22.2 No 60947-5-1
Timer Typeon delay
Rated Operational Voltage Limits0.85...1.1 Uc
[Ue] Rated Operational Voltage110...240 V AC control circuit || 240 V AC signalling circuit
Range CompatibilityTeSys K LC1K || TeSys K CA2K || TeSys K CA3K || TeSys K CA4K
Product Or Component Typetime delay auxiliary contact block
Product NameTeSys K

Contractual warranty

Warranty18 months

Complementary

Height27 mm
Insulation Resistance> 10 MOhm
Net Weight0.04 kg
Connections - Terminalsslip-on terminals
Reset Time1.5 s during time delay || 0.5 s after time delay
Width38 mm
Depth38 mm

Offer Sustainability

Rohs Exemption InformationYes
Mercury FreeYes
Environmental DisclosureENVPEP2106022
Sustainable Offer StatusGreen Premium product
Reach RegulationReference contains Substances of Very High Concern above the threshold
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs RegulationProduct out of China RoHS scope. Substance declaration for your information.
Eu Rohs DirectiveCompliant

Environment

Ambient Air Temperature For Operation-10-60 °C
Ip Degree Of ProtectionIP20 conforming to IEC 60529
Environmental Characteristicnormal environment
Protective TreatmentTC IEC 60068