Cam stepping switch, Harmony K, Ø16 or 22mm, plastic, 1 poles,position 0, 4 steps+position 0, 30°, 10A, 30x30mm, marked 0/1/2/3/4
- Produttore:
- Schneider Electric
- Prezzo (IVA esclusa)
- € 30.82
- Codice Nuova Elva
- K10D004QCH
- Codice produttore
- K10D004QCH
- Disponibilità
- Invia RdO
This Harmony K10 cam stepping switch has 1 pole (1P). It also has a rating of 10A, a screw clamp mounting mode and a metallic color with black marking. It has "0 - 1 - 2 - 3 - 4" marking to indicate the position of the switch. This metal head cam stepping switch is designed to meet most industrial and process control application thanks to a compact size, an easy integration with 16mm and 22mm diameter units and has several selection functions. It has a 30 degree between its switching positions. IP65 on its front part allows for installation in harsh (heavy) environment or outdoor.
Specifications
Certifications | CULus |
---|---|
Net Weight | 0.045 kg |
Number of Steps | 4 |
Standard | CENELEC EN 50013 |
Storage Temperature | -40-70 °C |
Warranty Length | 18 months |
Specifications | |
Range Of Product | Harmony K |
Switching Positions | right: 270° - 300° - 330° - 0° - 30° |
Cam Switch Head Type | with front plate 30 x 30 mm |
Product Mounting | front mounting |
Poles Description | 1P |
Rotary Handle Padlocking | without |
Return | without |
Off Position | with Off position |
Fixing Mode | Ø 16 or 22 mm hole |
Presentation Of Legend | with metallic, 0 - 1 - 2 - 3 - 4 black |
Ip Degree Of Protection | contact block IP20 || operating head IP65 IEC 60529 |
Product Or Component Type | complete cam switch |
[Ith] Conventional Free Air Thermal Current | 10 A |
Cam Switch Function | stepping switch |
Component Name | K10 |
Type Of Operator | Black handle |
Contractual warranty | |
Warranty | 18 months |
Complementary | |
Short-Circuit Protection | 10 A cartridge fuse gG |
Contact Operation | slow-break |
Mechanical Durability | 1000000 cycles |
Rated Power In Hp | 0.33 hp 110/120 V AC, 1 phase || 0.75 hp 220/240 V AC, 1 phase |
[Ie] Rated Operational Current Dc | 10 A 24 V resistive || 0.3 A 220 V resistive || 0.7 A 110 V resistive |
Cad Overall Width | 30 mm |
Cad Overall Depth | 88 mm |
Rated Operational Power In W | 370 W AC-23A, 110/120 V 1 phase || 750 W AC-23A, 220/240 V 1 phase |
[Ie] Rated Operational Current Ac | 10 A 400 V AC-1 || 10 A 400 V AC-21A || 3 A 240 V AC-15 || 6 A 120 V AC-15 |
Number Of Steps | 4 |
Net Weight | 0.045 kg |
[Uimp] Rated Impulse Withstand Voltage | 4 kV IEC 60947-1 |
Cad Overall Height | 30 mm |
Switching Angle | 30 ° |
Electrical Connection | captive screw clamp terminals 2 x 1.5 mm² |
Electrical Durability | 100000000 cycles |
[Ui] Rated Insulation Voltage | 440 V 3)IEC 60947-1 |
Offer Sustainability | |
Rohs Exemption Information | Yes |
Mercury Free | Yes |
Toxic Heavy Metal Free | Yes |
Reach Regulation | Free of Substances of Very High Concern above the threshold |
California Proposition 65 | WARNING: This product can expose you to chemicals including: Nickel compounds, which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov |
Reach Free Of Svhc | Yes |
Weee | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
China Rohs Regulation | X |
Eu Rohs Directive | Pro-active compliance (Product out of EU RoHS legal scope) |
Environment | |
Ambient Air Temperature For Operation | -20-55 °C |
Product Certifications | cULus |
Standards | CENELEC EN 50013 || EN/IEC 60947-3 || EN/IEC 60947-5-1 |
Ambient Air Temperature For Storage | -40-70 °C |
Electrical Shock Protection Class | class II IEC 60536 |
Protective Treatment | TC |