Circuit breaker, PowerPacT H, 50A, 3 pole, 600VAC, 14kA, lugs, thermal magnetic, 80%

Produttore:
Schneider Electric
Schneider%20electric

F0e5cdf0ec6f52570bc4dab9265d253c8eb16499 medium
Prezzo (IVA esclusa)
€ 1206.90
Codice Nuova Elva
HDL36050
Codice produttore
HDL36050
Disponibilità
Invia RdO

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 14kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has lugs on both the line and load sides. This PowerPacT H, 50A, 3 pole, circuit breaker has a breaking capacity of 14kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.

Specifications

CertificationsCSA
ColorBlack
Depth86 mm
Height163 mm
Line Rated Current50-50 A
Mounting TypeUnit Mount Lug)
Net Weight2.2 kg
StandardCSA
Storage Temperature-50-85 °C
Strip Length16 mm
Trip Point850-850 A
Warranty Length18 months
Width104 mm

Specifications

Product Or Component Typecircuit breaker
Product NamePowerPact H
RangePowerPact
Device Applicationdistribution

Contractual warranty

Warranty18 months

Complementary

Mounting Modeunit mount lug)
Breaking Capacity CodeD
Magnetic Tripping Current850-850 A
Local Signallingswitched off (OFF) 1 trip indicator green)
Number Of Slots2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Protected Poles Description3t
Electrical Connectionlugs line || lugs load
Net Weight2.2 kg
[Uimp] Rated Impulse Withstand Voltage8 kV IEC 60947-2
Magnetic Hold Current400 A
Control Typetoggle
Network Frequency50/60 Hz
Circuit Breaker ApplicationHACR rated
Wire Stripping Length16 mm
Utilisation Categorycategory A
Line Rated Current50-50 A
Continuous Current Rating80 %
Breaking Capacity25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
[Ui] Rated Insulation Voltage750 V IEC 60947-2
Suitability For Isolationyes IEC 60947-2
Communication InterfaceModbus || Ethernet
Poles Description3P
Terminal IdentifierAL150HD
Quantity Per Set1
Awg GaugeAWG 14...AWG 3/0 aluminium/copper terminal
ColorBlack
Width104 mm
Depth86 mm
[Ics] Rated Service Breaking Capacity25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Trip Unit Technologythermal-magnetic
Height163 mm
[Ue] Rated Operational Voltage690 V AC 50/60 Hz IEC 60947-3
Tightening Torque5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Mounting Supportlug

Offer Sustainability

Rohs Exemption InformationYes
Circularity ProfileENVEOLI2206027EN
Eu Rohs DirectiveCompliant
Mercury FreeYes
Environmental DisclosureENVPEP2206027EN
Sustainable Offer StatusGreen Premium product
Pvc FreeYes
Reach RegulationReference contains Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs RegulationProduct out of China RoHS scope. Substance declaration for your information.

Environment

Ambient Air Temperature For Operation-2-70 °C
StandardsUL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Product CertificationsUL || CSA || NOM
Ip Degree Of Protectionfront cover IP40 IEC 60529
Pollution Degree3 IEC 60947-1
Ambient Air Temperature For Storage-50-85 °C
Quality LabelsCE
Operating Altitude< 6561.68 ft (2000 m) without derating || 5000 m with derating

Documentazione