T6N 800 PR222DS/P-LSI In=800 3p F F

Produttore:
ABB
Abb

E459f2ace0aa9eab8b1adb87786a3b6cbf2432c4 medium
Prezzo (IVA esclusa)
€ 4422.60
Codice Nuova Elva
1SDA060270R1
Codice produttore
1SDA060270R1
Disponibilità
Tempo di consegna standard: 5 giorni

C.BREAKER TMAX T6N 800 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC PR222DS/P-LSI R 800

Specifications

Ordering

E-Number (Finland)3655436
Minimum Order Quantity1 piece
Customs Tariff Number85362090

Dimensions

Product Net Width210 mm
Product Net Height268 mm
Product Net Depth / Length103.5 mm
Product Net Weight9.5 kg

Container Information

Package Level 1 Depth / Length370 mm
Package Level 1 Gross Weight11 kg
Package Level 1 EAN8015644627324
Package Level 1 Units1 piece
Package Level 1 Width305 mm
Package Level 1 Height285 mm

Additional Information

Electrical Durability5000 cycle60 cycles per hour
Mechanical Durability20000 cycle120 cycles per hour
Number of Poles3
Power Lossat Rated Operating Conditions per Pole 32 W
Product Main TypeSACE Tmax T
Product NameMoulded Case Circuit Breaker
Product TypeCB
Rated Current (In)Main Circuit 800 A
Rated Impulse Withstand Voltage (Uimp)8 kV
Rated Insulation Voltage (Ui)1000 V
Rated Operational Voltage690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)(220 V AC) 70 kA(230 V AC) 70 kA(380 V AC) 36 kA(400 V AC) 36 kA(415 V AC) 36 kA(440 V AC) 30 kA(500 V AC) 25 kA(690 V AC) 15 kA
Rated Short-time Withstand Current (Icw)for 1 s 10 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(220 V AC) 70 kA(230 V AC) 70 kA(380 V AC) 36 kA(400 V AC) 36 kA(415 V AC) 36 kA(440 V AC) 30 kA(500 V AC) 25 kA(690 V AC) 20 kA
Rated Uninterrupted Current (Iu)800 A
ReleasePR222DS/P-LSI
Release TypeEL
Short-Circuit Performance LevelN
StandardsIEC
Sub-typeT6
Suitable ForT6
Suitable for Product ClassMoulded Case Circuit Breakers
Terminal Connection TypeFixed Circuit-BreakersFront
Test Voltage Max (Utest)3500 V
VersionF

Classifications

ETIM 4EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 5EC000228 - Power circuit-breaker for trafo/generator/installation prot.
Object Classification CodeQ
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)