XT2H 160 Ekip LS/I In=63A 4p F F

Manufactured by:
ABB
Abb

E616be4230724d2d504583a83d9bf69029941a70 medium
Nuova Elva code
XT2H63LSI4
Manufacturer code
1SDA067892R1
Availability
Send request for quotation

C.BREAKER TMAX XT2H 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP-LS/I R 63 A

Specifications

Ordering

Minimum Order Quantity1 piece
Customs Tariff Number85362090

Dimensions

Product Net Width120 mm
Product Net Height130 mm
Product Net Depth / Length82.5 mm
Product Net Weight1.5 kg

Container Information

Package Level 1 Gross Weight1.6 kg
Package Level 1 EAN8015644017880
Package Level 1 Units1 piece
Package Level 1 Width130 mm
Package Level 1 Height208 mm
Package Level 1 Depth / Length145 mm

Environmental

RoHS StatusFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Additional Information

Circuit Breaker Type to be AssociatedPower Distribution
Current TypeAC
Electrical Durability120 cycles per hour8000 cycle
Mechanical DurabilityNr. Operations 240 cycles per hourNr. Operations 25000 cycle
Number of Poles4
Opening TimeCB with SOR 15 msCB with UVR 15 ms
Order Multiple1 piece
Product Main TypeSACE Tmax XT
Product NameMoulded Case Circuit Breaker
Product TypeCB
Rated Current (In)63 A
Rated Frequency (f)50 / 60 Hz
Rated Voltage (Ur)690 V
Rated Impulse Withstand Voltage (Uimp)8 kV
Rated Insulation Voltage (Ui)1000 V
Rated Operational Voltage690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)(220 V AC) 100 kA(230 V AC) 100 kA(240 V AC) 100 kA(380 V AC) 70 kA(415 V AC) 70 kA(440 V AC) 65 kA(500 V AC) 50 kA(525 V AC) 30 kA(690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(220 V AC) 100 kA(230 V AC) 100 kA(240 V AC) 100 kA(380 V AC) 70 kA(415 V AC) 70 kA(440 V AC) 65 kA(500 V AC) 50 kA(525 V AC) 30 kA(690 V AC) 15 kA
Rated Uninterrupted Current (Iu)160 A
ReleaseEkip LS/I
Release TypeEL
Short-Circuit Performance LevelH
StandardsIEC
Sub-typeXT2
Terminal Connection TypeFixed Circuit-Breakers
VersionF

Classifications

ETIM 4EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 5EC000228 - Power circuit-breaker for trafo/generator/installation prot.
Object Classification CodeQ
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)

Other ABB items

Request a quote