NF40E-14 250-500V50/60HZ-DC Contactor Relay

Manufactured by:
ABB
Abb

069210d9073ced62bbd363735c902a0b02f62103 medium
Nuova Elva code
NF40E14
Manufacturer code
1SBH137001R1440
Availability
Standard lead time: 16 days

NF contactor relays are used for switching auxiliary and control circuits. NF contactor relays include an electronic coil interface accepting a wide control voltage Uc min. ... Uc max. Only four coils cover control voltages between 24...500 V 50/60 Hz or 20...500 V DC. NF contactor relays can manage large control voltage variations. One coil can be used for different control voltages used worldwide without any coil change. NF contactor relays have built-in surge protection and do not require additional surge suppressors. - Poles: 4-pole contactor relays - Control Circuit: AC or DC operated - Accessories: a wide range of Accessories is available.

Specifications

Ordering

Minimum Order Quantity1 piece
Customs Tariff Number85364900

Dimensions

Product Net Width45 mm
Product Net Depth / Length77 mm
Product Net Height86 mm
Product Net Weight0.31 kg

Technical

Rated Frequency (f)Auxiliary Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-5-1, q = 40 °C 16 A
Rated Operational Current AC-15 (Ie)(500 V) 2 A(690 V) 2 A(24 / 127 V) 6 A(220 / 240 V) 4 A(400 / 440 V) 3 A
Rated Short-time Withstand Current (Icw)for 0.1 s 140 Afor 1 s 100 A
Maximum Electrical Switching Frequency(AC-15) 1200 cycles per hour(DC-13) 900 cycles per hour
Rated Operational Current DC-13 (Ie)(24 V) 6 A / 144 W(48 V) 2.8 A / 134 W(72 V) 1 A / 72 W(110 V) 0.55 A / 60 W(125 V) 0.55 A / 69 W(220 V) 0.27 A / 60 W(250 V) 0.27 A / 68 W(400 V) 0.15 A / 60 W(500 V) 0.13 A / 65 W(600 V) 0.1 A / 60 W
Rated Insulation Voltage (Ui)acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 Vacc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)6 kV
Maximum Mechanical Switching Frequency6000 cycles per hour
Rated Control Circuit Voltage (Uc)50 Hz 250 ... 500 V50 Hz / 60 Hz 250 ... 500 V60 Hz 250 ... 500 VDC Operation 250 ... 500 V
Operate TimeBetween Coil De-energization and NC Contact Closing 13 ... 98 msBetween Coil De-energization and NO Contact Opening 11 ... 95 msBetween Coil Energization and NC Contact Opening 38 ... 90 msBetween Coil Energization and NO Contact Closing 40 ... 95 ms
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²Rigid 1/2x 1 ... 2.5 mm²
Connecting Capacity Control CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²Rigid 1/2x 1 ... 2.5 mm²
Wire Stripping LengthAuxiliary Circuit 10 mmControl Circuit 10 mm
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP40acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
Terminal TypeScrew Terminals
Number of Auxiliary Contacts NO4
Number of Auxiliary Contacts NC0
StandardsIEC 60947-5-1 and EN 60947-5-1, UL 508, CSA C22.2 N°14
Rated Operational VoltageAuxiliary Circuit 690 VMain Circuit 690 V

Technical UL/CSA

Tightening Torque UL/CSAAuxiliary Circuit 11 IAControl Circuit 11 IA

Environmental

Ambient Air TemperatureClose to Contactor for Storage -60 ... +80 °CNear Contactor for Operation in Free Air -40 ... +70 °C
Climatic WithstandCategory B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible3000 m
Resistance to Vibrations acc. to IEC 60068-2-65 ... 300 Hz 4 g closed position / 2 g open position
Resistance to Shock acc. to IEC 60068-2-27Closed, Shock Direction: B1 25 K40Open, Shock Direction: B1 5 K40Shock Direction: A 30 K40Shock Direction: B2 15 K40Shock Direction: C1 25 K40Shock Direction: C2 25 K40
RoHS StatusFollowing EU Directive 2011/65/EU

Container Information

Package Level 1 Unitsbox 1 piece
Package Level 1 Width87 mm
Package Level 1 Depth / Length79 mm
Package Level 1 Height47 mm
Package Level 1 Gross Weight0.31 kg
Package Level 1 EAN3471523100046
Package Level 2 Unitsbox 27 piece
Package Level 2 Width250 mm
Package Level 2 Depth / Length300 mm
Package Level 2 Height315 mm
Package Level 2 Gross Weight16.74 kg
Package Level 3 Units1296 piece

Classifications

Object Classification CodeK
ETIM 4EC000196 - Contactor relay
ETIM 5EC000196 - Contactor relay
eClassV11.0 : 27371003
E-Number (Finland)3706416
E-Number (Sweden)3211457

Docs


Other ABB items

Request a quote