GAF460-10-11 100-250V 50/60Hz / 100-250V DC Contactor

Manufactured by:
ABB
Abb

018f3f971490002a31c2a1065652c089353ca391 medium
Nuova Elva code
GAF4601011230
Manufacturer code
1SFL597025R7011
Availability
Standard lead time: 15 days

A 3-pole Contactor suitable for DC-1 applications where all three poles must be connected in series in a 1-pole configuration up to max 1000 VDC. Operated with wide control voltage range 100-250 V, AC/DC

Specifications

Ordering

Minimum Order Quantity1 piece
Customs Tariff Number85364900

Dimensions

Product Net Width186 mm
Product Net Depth / Length216 mm
Product Net Height278 mm
Product Net Weight10.6 kg

Technical

Rated Operational VoltageMain Circuit 1000 V
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-4-1, Open Contactors q = 40 °C 700 A
Rated Operational Current DC-1 (Ie)(1000 V) 3 Poles in Series, 40 °C 700 A(1000 V) 3 Poles in Series, 55 °C 600 A(1000 V) 3 Poles in Series, 70 °C 480 A(220 V) 3 Poles in Series, 40 °C 700 A(220 V) 3 Poles in Series, 55 °C 600 A(220 V) 3 Poles in Series, 70 °C 480 A(400 V) 3 Poles in Series, 40 °C 700 A(400 V) 3 Poles in Series, 55 °C 600 A(400 V) 3 Poles in Series, 70 °C 480 A(600 V) 3 Poles in Series, 40 °C 700 A(600 V) 3 Poles in Series, 55 °C 600 A(600 V) 3 Poles in Series, 70 °C 480 A
Rated Insulation Voltage (Ui)acc. to UL/CSA 1000 V
Rated Impulse Withstand Voltage (Uimp)Main Circuit 8 kV
Mechanical Durability5 million
Maximum Mechanical Switching Frequency300 cycles per hour
Coil Operating Limits(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc)50 Hz 100 ... 250 V60 Hz 100 ... 250 VDC Operation 100 ... 250 V
Coil ConsumptionHolding at Max. Rated Control Circuit Voltage 50 Hz 12 V·AHolding at Max. Rated Control Circuit Voltage 60 Hz 12 V·AHolding at Max. Rated Control Circuit Voltage DC 4 WPull-in at Max. Rated Control Circuit Voltage 50 Hz 890 V·APull-in at Max. Rated Control Circuit Voltage 60 Hz 890 V·APull-in at Max. Rated Control Circuit Voltage DC 990 W
Connecting Capacity Main CircuitBar 47 mm²Rigid Al-Cable 2x240 mm²Rigid Cu-Cable 240 mm²
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²Flexible 2x0.75 ... 2.5 mm²Solid 2 x 1 ... 4 mm²Stranded 1 x 1 .... 4 mm²
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal TypeMain Circuit: Bars
Number of Main Contacts NO1
Number of Main Contacts NC0
Number of Auxiliary Contacts NO1
Number of Auxiliary Contacts NC1

Technical UL/CSA

Maximum Operating Voltage UL/CSAMain Circuit 600 V
General Use Rating UL/CSA(1000 V DC) 650 A(440 V DC) 650 A(600 V DC) 650 A

Environmental

Ambient Air TemperatureOperation -40 ... +80 °CStorage -40 ... +70 °C
Maximum Operating Altitude Permissible3000 m
Resistance to Shock acc. to IEC 60068-2-27Shock Direction: A 5 K40Shock Direction: B1 5 K40Shock Direction: B2 5 K40Shock Direction: C1 5 K40Shock Direction: C2 5 K40
RoHS StatusFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Container Information

Package Level 1 Unitsbox 1 piece
Package Level 1 Width280 mm
Package Level 1 Depth / Length375 mm
Package Level 1 Height310 mm
Package Level 1 Gross Weight12 kg
Package Level 1 EAN7320500383971

Classifications

Object Classification CodeQ
ETIM 4EC002552 - Power contactor, DC switching
ETIM 5EC002552 - Power contactor, DC switching
eClassV11.0 : 27371018
IDEA Granular Category Code (IGCC)4763 >> Power contactor, DC switching

Docs


Other ABB items

Request a quote