GAF1250-10-11 48-130V 50/60Hz / 48-130V DC Contactor

Manufactured by:
ABB
Abb

8606e2bd7848ae2b70d2901b50e2ce13f3cbfaaf medium
Nuova Elva code
GAF12501011110
Manufacturer code
1SFL647025R6911
Availability
Send request for quotation

A 3-pole Contactor suitable for DC-1 applications where all three poles must be connected in series in a 1-pole configuration up to max 1000 VDC. Operated with wide control voltage range 48-130 V, AC/DC

Specifications

Ordering

Minimum Order Quantity1 piece
Customs Tariff Number85364900

Dimensions

Product Net Width210 mm
Product Net Depth / Length242 mm
Product Net Height344 mm
Product Net Weight15 kg

Technical

Rated Operational VoltageMain Circuit 1000 V
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-4-1, Open Contactors q = 40 °C 1260 A
Rated Operational Current DC-1 (Ie)(1000 V) 3 Poles in Series, 40 °C 1250 A(1000 V) 3 Poles in Series, 55 °C 1040 A(1000 V) 3 Poles in Series, 70 °C 875 A(220 V) 3 Poles in Series, 40 °C 1250 A(220 V) 3 Poles in Series, 55 °C 1040 A(220 V) 3 Poles in Series, 70 °C 875 A(400 V) 3 Poles in Series, 40 °C 1250 A(400 V) 3 Poles in Series, 55 °C 1040 A(400 V) 3 Poles in Series, 70 °C 875 A(600 V) 3 Poles in Series, 40 °C 1250 A(600 V) 3 Poles in Series, 55 °C 1040 A(600 V) 3 Poles in Series, 70 °C 875 A
Rated Insulation Voltage (Ui)acc. to UL/CSA 1000 V
Rated Impulse Withstand Voltage (Uimp)Main Circuit 8 kV
Mechanical Durability0.5 million
Maximum Mechanical Switching Frequency300 cycles per hour
Coil Operating Limits(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc)50 Hz 48 ... 130 V60 Hz 48 ... 130 VDC Operation 48 ... 130 V
Coil ConsumptionHolding at Max. Rated Control Circuit Voltage 50 Hz 12 V·AHolding at Max. Rated Control Circuit Voltage 60 Hz 12 V·AHolding at Max. Rated Control Circuit Voltage DC 4.5 WPull-in at Max. Rated Control Circuit Voltage 50 Hz 850 V·APull-in at Max. Rated Control Circuit Voltage 60 Hz 850 V·APull-in at Max. Rated Control Circuit Voltage DC 950 W
Connecting Capacity Main CircuitBar 50 mm²
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²Flexible 2x0.75 ... 2.5 mm²Solid 1 x 1 ... 4 mm²Stranded 1 x 1 .... 4 mm²
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal TypeMain Circuit: Bars
Number of Main Contacts NO1
Number of Main Contacts NC0
Number of Auxiliary Contacts NO1
Number of Auxiliary Contacts NC1

Technical UL/CSA

Maximum Operating Voltage UL/CSAMain Circuit 600 V
General Use Rating UL/CSA(1000 V DC) 1210 A(440 V DC) 1210 A(600 V DC) 1210 A

Environmental

Ambient Air TemperatureOperation -40 ... +80 °CStorage -40 ... +70 °C
Maximum Operating Altitude Permissible3000 m
Resistance to Shock acc. to IEC 60068-2-27Shock Direction: A 5 K40Shock Direction: B1 5 K40Shock Direction: B2 5 K40Shock Direction: C1 5 K40Shock Direction: C2 5 K40
RoHS StatusFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Container Information

Package Level 1 Unitsbox 1 piece
Package Level 1 Width280 mm
Package Level 1 Depth / Length375 mm
Package Level 1 Height310 mm
Package Level 1 Gross Weight16 kg
Package Level 1 EAN7320500400814

Classifications

Object Classification CodeQ
ETIM 4EC002552 - Power contactor, DC switching
ETIM 5EC002552 - Power contactor, DC switching
eClassV11.0 : 27371018
IDEA Granular Category Code (IGCC)4763 >> Power contactor, DC switching

Docs


Other ABB items

Request a quote