DDA203 AC-25/0,03 - RCD Block

Manufactured by:
ABB
Abb

Df9b78de25de48e2ba5e60a69bc03410ec2937b4 medium
Nuova Elva code
B427925
Manufacturer code
2CSB203001R1250
Availability
Standard lead time: 24 days

The RCD block DDA200 series is suitable for assembly with MCBs S200 series. It assures protection against the effects of sinusoidal alternating earth fault currents, protection, against indirects contacts and additional protection against direct (with sensitivity = 30 mA) contacts. Applications: residential, commercial, industrial.

Specifications

Technical

StandardsIEC/EN 61009 Ann. G
Operating CharacteristicInstantaneous
Type of Residual CurrentAC type
Rated Residual Current30 mA
Rated Current (In)25 A
Number of Poles3
Power Loss3 W
Rated Voltage (Ur)230/400 V

Environmental

Ambient Air TemperatureOperation -25...55 °C
RoHS StatusFollowing EU Directive 2011/65/EU

Technical UL/CSA

Short-Circuit Current Rating (SCCR)0,03 ... 0,03 A

Dimensions

Product Net Width0.087 m
Product Net Height0.093 m
Product Net Depth / Length0.069 m
Product Net Weight0.158 kg

Container Information

Package Level 1 Units1 piece
Package Level 1 Width0.096 m
Package Level 1 Height0.075 m
Package Level 1 Depth / Length0.102 m
Package Level 1 Gross Weight0.199 kg
Package Level 1 EAN8012542792512

Ordering

Minimum Order Quantity1 piece
Customs Tariff Number85363030

Classifications

Object Classification CodeQ
ETIM 4EC002297 - Residual current circuit breaker (RCCB) module
ETIM 5EC002297 - Residual current circuit breaker (RCCB) module
ETIM 6EC002297 - Residual current circuit breaker (RCCB) module
ETIM 7EC002297 - Residual current circuit breaker (RCCB) module

Docs