TeSys Vario enclosed, emergency switch disconnector, 16A, IP65

Produttore:
Schneider Electric
Schneider%20electric

Telvcf01ge%7c001
Prezzo (IVA esclusa)
€ 58.10
Codice Nuova Elva
VCF01GE
Codice produttore
VCF01GE
Disponibilità
Invia RdO

TeSys enclosed starter with switch disconnector, 3 poles, Ithe 16A 690V, for main and emergency stop switching in motor applications AC-23 up to 5.5kW@400V. Enclosure providing IP65 protection, fitted with a red rotary handle and yellow front plate, padlockable (padlocks not included). It includes a 3-pole Vario switch body V01 with 2 possible add-on module attachments. Surface mounting enclosure with screw fixing, 2 knock-outs for cable glands on top and bottom, sealable cover. It conforms to IEC 60204 and IEC 60947-4-1, Green Premium compliant (RoHS/REACh).

Specifications

Depth131 mm
Height146 mm
Net Weight0.5 kg
StandardIEC 60204
Warranty Length18 months
Width90 mm

Specifications

Rotary Handle Padlocking1 to 3 padlocks 4-8 mm
Device Short NameVCF
Handle Front Plate Colouryellow
Handle Colourred
Product Or Component Typeenclosed emergency stop switch disconnector
Product NameTeSys VARIO
Performance Levelhigh performance
RangeTeSys
Control Typerotary handle
Poles Description3P

Contractual warranty

Warranty18 months

Complementary

[Ue] Rated Operational Voltage690 V AC
Connections - Terminalsscrew clamp terminals 10-10 mm² solid || screw clamp terminals 6-6 mm² flexible - with cable end
[Icm] Rated Short-Circuit Making Capacity1 kA 400 V at Ipeak
Electrical Durability100000 cycles AC-21 || 30000 cycles DC-1...5
Environmental Characteristicstandard environment
Suitability For Isolationyes
[Ie] Rated Operational Current11 A AC-23A)400 V
Mechanical Durability100000 cycles
Fire Resistance960 °C IEC 60595-2-1
Width90 mm
Tightening Torque2.1-2.1 N.m screw clamp terminals
Height146 mm
Depth131 mm
Breaking Capacity200 A 400 V AC-21A) || 200 A 400 V AC-22A) || 200 A 400 V AC-23A)
Rated Operational Power In W5.5 kW 400 V AC-23) || 4 kW 400 V AC-3)
Rated Conditional Short-Circuit Current10 kA 400 V 20 A aM || 10 kA 400 V 20 A gG
[Icw] Rated Short-Time Withstand Current300 A 400 V 1 s
Intermittent Duty Class30
[Ithe] Conventional Enclosed Thermal Current16 A
Marking0 - 1
Base Dimension60 x 60 mm
Net Weight0.5 kg
[Uimp] Rated Impulse Withstand Voltage8 kV
Making Capacity200 A 400 V AC-21A || 200 A 400 V AC-22A || 200 A 400 V AC-23A

Offer Sustainability

Rohs Exemption InformationYes
China Rohs RegulationProduct out of China RoHS scope. Substance declaration for your information.
Eu Rohs DirectiveCompliant
Mercury FreeYes
Environmental DisclosureENVPEP111273EN
Sustainable Offer StatusGreen Premium product
Toxic Heavy Metal FreeYes
Reach RegulationFree of Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of SvhcYes
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.

Environment

Ambient Air Temperature For Operation-20-50 °C
StandardsIEC 60947-4-1 || IEC 60204
Ip Degree Of ProtectionIP65 conforming to IEC 60529
Protective TreatmentTC
Mechanical Robustnessvibrations 10...150 Hz 1 gn) IEC 60068-2-6 || shocks 11 ms 30 Gn) IEC 60068-2-27

Documentazione


Spesso acquistati assieme


Altri articoli da Schneider Electric

Richiedi un preventivo