IEC contactor, TeSys Deca, nonreversing, 32A, 20HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 24VDC coil, open style

Produttore:
Schneider Electric
Schneider%20electric

D1d93ed5574b4f6f66f9bd8b7b8d6d62e10b3c73 medium
Prezzo (IVA esclusa)
€ 165.78
Codice Nuova Elva
LC1D32BD
Codice produttore
LC1D32BD
Disponibilità
3 in stock

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 32A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 80A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.98 inches deep. It weighs 1.18 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.

Specifications

CertificationsBV
Contact Configuration1 NO + 1 NC
Depth101 mm
Height85 mm
Impedance2 MOhm - Ith 50 A 50 Hz Power Circuit
Net Weight0.535 kg
StandardCSA C22.2 No 14
Warranty Length18 months
Width45 mm

Specifications

[Uc] Control Circuit Voltage24 V DC
[Ue] Rated Operational Voltagepower circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Range Of ProductTeSys Deca
Contactor Applicationresistive load || motor control
Product Or Component Typecontactor
Utilisation CategoryAC-3 || AC-1 || AC-4 || AC-3e
[Ie] Rated Operational Current32 A 60 °C) <= 440 V AC AC-3 power circuit || 50 A 60 °C) <= 440 V AC AC-1 power circuit || 32 A 60 °C) <= 440 V AC AC-3e power circuit
Poles Description3P
Device Short NameLC1D

Contractual warranty

Warranty18 months

Complementary

Non-Overlap Time1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Control Circuit TypeDC standard
Safety Reliability LevelB10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Pollution Degree3
Hold-In Power Consumption In W5.4-5.4 W 20 °C
Insulation Resistance> 10 MOhm signalling circuit
Rated Breaking Capacity550 A 440 V power circuit IEC 60947
Irms Rated Making Capacity140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 550 A 440 V power circuit IEC 60947
Associated Fuse Rating10 A gG signalling circuit IEC 60947-5-1 || 63 A gG <= 690 V type 1 power circuit || 63 A gG <= 690 V type 2 power circuit
[Uimp] Rated Impulse Withstand Voltage6 kV IEC 60947
Pole Contact Composition3 NO
Minimum Switching Current5 mA signalling circuit
Connections - Terminalscontrol circuit screw clamp terminals 1 1-4 mm² flexible without cable end || control circuit screw clamp terminals 2 1-4 mm² flexible without cable end || control circuit screw clamp terminals 1 1-4 mm² flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm² flexible with cable end || control circuit screw clamp terminals 1 1-4 mm² solid without cable end || control circuit screw clamp terminals 2 1-4 mm² solid without cable end || power circuit screw clamp terminals 1 2.5-10 mm² flexible without cable end || power circuit screw clamp terminals 2 2.5-10 mm² flexible without cable end || power circuit screw clamp terminals 1 1-10 mm² flexible with cable end || power circuit screw clamp terminals 2 1.5-6 mm² flexible with cable end || power circuit screw clamp terminals 1 1.5-10 mm² solid without cable end || power circuit screw clamp terminals 2 2.5-10 mm² solid without cable end
Coil Technologybuilt-in bidirectional peak limiting diode suppressor
Time Constant28 ms
Operating Time53.55...72.45 ms closing || 16...24 ms opening
Minimum Switching Voltage17 V signalling circuit
Maximum Operating Rate3600 cyc/h 60 °C
Signalling Circuit Frequency25...400 Hz
Tightening Torquecontrol circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 2.5 N.m screw clamp terminals flat Ø 6 mm || power circuit 2.5 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2
Electrical Durability1.65 Mcycles 32 A AC-3 <= 440 V || 1.4 Mcycles 50 A AC-1 <= 440 V || 1.65 Mcycles 32 A AC-3e <= 440 V
Mechanical Durability30 Mcycles
Power Dissipation Per Pole2 W AC-3 || 5 W AC-1 || 2 W AC-3e
Inrush Power In W5.4-5.4 W 20 °C)
Auxiliary Contacts Typemechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Compatibility CodeLC1D
Overvoltage CategoryIII
Maximum Horse Power Rating2 hp 115 V at AC 50/60 Hz for 1 phase || 5 hp 230/240 V at AC 50/60 Hz for 1 phase || 7.5 hp 200/208 V at AC 50/60 Hz for 3 phase || 10 hp 230/240 V at AC 50/60 Hz for 3 phase || 20 hp 460/480 V at AC 50/60 Hz for 3 phase || 30 hp 575/600 V at AC 50/60 Hz for 3 phase
Motor Power Kw7.5 kW 220...230 V AC 50/60 Hz AC-3) || 15 kW 380...400 V AC 50/60 Hz AC-3) || 15 kW 415...440 V AC 50/60 Hz AC-3) || 18.5 kW 500 V AC 50/60 Hz AC-3) || 18.5 kW 660...690 V AC 50/60 Hz AC-3) || 7.5 kW 400 V AC 50/60 Hz AC-4) || 7.5 kW 220...230 V AC 50/60 Hz AC-3e) || 15 kW 380...400 V AC 50/60 Hz AC-3e) || 15 kW 415...440 V AC 50/60 Hz AC-3e) || 18.5 kW 500 V AC 50/60 Hz AC-3e) || 18.5 kW 660...690 V AC 50/60 Hz AC-3e)
[Ui] Rated Insulation Voltagepower circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
[Icw] Rated Short-Time Withstand Current260 A 40 °C - 10 s power circuit || 430 A 40 °C - 1 s power circuit || 60 A 40 °C - 10 min power circuit || 138 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
Protective Coverwith
Average Impedance2 mOhm - Ith 50 A 50 Hz power circuit
Auxiliary Contact Composition1 NO + 1 NC
[Ith] Conventional Free Air Thermal Current10 A 60 °C signalling circuit || 50 A 60 °C power circuit
Control Circuit Voltage Limits0.1...0.25 Uc -40-70 °C drop-out DC || 0.7...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC
Mounting Supportrail || plate
Contact CompatibilityM4

Offer Sustainability

Rohs Exemption InformationYes
Eu Rohs DirectiveCompliant
Mercury FreeYes
Environmental DisclosureENVPEP110230EN
Sustainable Offer StatusGreen Premium product
Pvc FreeYes
Reach RegulationReference contains Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
China Rohs RegulationProduct out of China RoHS scope. Substance declaration for your information.
Circularity ProfileENVEOLI1102030EN

Environment

Product CertificationsDNV || GL || CCC || UL || GOST || BV || LROS (Lloyds register of shipping) || RINA || CSA || UKCA
Operating Altitude0...9842.52 ft (0...3000 m)
Fire Resistance850 °C IEC 60695-2-1
Width45 mm
Depth101 mm
Permissible Ambient Air Temperature Around The Device-40-60 °C || 60-70 °C with derating
Height85 mm
StandardsCSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Climatic WithstandIACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Net Weight0.535 kg
Flame RetardanceV1 conforming to UL 94
Protective TreatmentTHIEC 60068-2-30
Ip Degree Of ProtectionIP20 front face IEC 60529
Mechanical Robustnessvibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 8 Gn for 11 ms)

Documentazione


Spesso acquistati assieme


Articoli correlati


Richiedi un preventivo