Sinamics G120 CU240E-2 PN

Produttore:
SIEMENS
Siemens

11ed8abfbc446290c176b8c38265fbe55921e339 medium
Prezzo (IVA esclusa)
€ 500.40
Codice Nuova Elva
6SL32440BB121FA0
Codice produttore
6SL3244-0BB12-1FA0
Disponibilità
Invia RdO

Sinamics G120 Control Unit CU240E-2 PN E-Type Safety Integrated STO PROFINET 6DI, 3DO, 2AI, 2AO, MAX 1F-DI PTC/KTY Interface USB- and SD/MMC-Interface Protection IP20 Ambient Temperature 0 to +50 Degree C without Power Module and Panel

Specifications

CertificationsC-Tick
Current.5 A
Depth46 mm
Height199 mm
IP RatingIP20
Max. Current0.5 A
Max. Operating Temperature55 °C
Min. Operating Temperature-10 °C
Number of Inputs6
StandardC-Tick (RCM)
Weight.49 kg
Width73 mm

Specifications

Net Weight in Kg0.49
Ambient temperature [°F] during operation maximum NoteA derating of 3 K/1000 m has to be applied to the Control Units from an installation altitude of 1000 m above sea level
Protocol is supported PROFIBus protocolNo
Protocol is supported PROFINET CBA protocolNo
Protocol is supported PROFINET IO protocolNo
Protocol is supported PROFIsafe protocolYes
Protocol is supported SafetyBus p protocolNo
Protocol is supported SERCOS protocolNo
Protocol is supported SUCONET protocolNo
Protocol is supported TCP/IPYes
Relative humidity maximum [%]95
Relative humidity maximum NoteRH, condensation not permitted
Ambient temperature [°F] during operation minimum [°F]14
Type of analog inputDifferential input
Type of analog input NoteSwitchable between voltage (-10 ... +10 V) and current (0/4 ... 20 mA) using a DIP switch
Type of analog outputNon-isolated output
Type of analog output NoteSwitchable between voltage (0 ... 10 V) and current (0/4 ... 20 mA) using a parameter
Width [mm]73
Ambient temperature [°F] during storage maximum [°F]158
Ambient temperature [°F] during storage minimum [°F]-40
Application rangefor modular Sinamics G120 inverters.
AWG number as coded connectable conductor cross section for signal line maximum16
AWG number as coded connectable conductor cross section for signal line minimum30
Certificate of suitabilityUL, cUL, CE, C-Tick (RCM)
Certificate of suitability for CE markingLow-voltage directive 2006/95/EC
Connectable conductor cross-section for signal line maximum [mm2]1.5
SupplierSiemens AG
Connectable conductor cross-section for signal line minimum [mm2]0.05
Consumed current maximum [A]0.5
Cover versionNo cover necessary
Depth [mm]46
Design of the interface for bus system IntegratedPROFINET
Design of the interface for bus system Integrated Note2 x RJ45, device name storable on device, max. 100 Mbits/s (Full Duplex)
Design of the interface for control unitsBasic Operator Panel BOP-2 or Intelligent Operator Panel IOP
Design of the interface for PC interfaceUSB
Design of the interface of the control unit of the storage medium1 Sinamics Micro Memory Card (MMC) or 1 Sinamics SD Card
Design of the interface removable plug-in terminalsYes
Order number6SL3244-0BB12-1FA0
Design of the protective insulationPELV according to EN 50178, safe disconnection from the mains by double/reinforced isolation
Design of the sensor to detect the ambient temperature connectable1 motor temperature sensor input, sensors that can be connected: PTC, KTY and Thermo-Click, accuracy ±5 °C
Equipment marking acc. to DIN EN 81346-2K
Height [mm]199
Input current at digital standard inputs maximum [mA]15
Input voltage at analog inputs as voltage inputs for signal <0> to <1> [V]4
Input voltage at analog inputs as voltage inputs for signal <1> to <0> [V]1.6
Input voltage at digital standard inputs for signal <0> to <1> [V]11
Input voltage at digital standard inputs for signal <1> to <0> [V]5
Load at analog output when selecting operating mode: current mode maximum [Ohm]500
A/D resolution at the analog input [bit]10
Load at analog output when selecting operating mode: voltage mode minimum [kOhm]10
Net weight [kg]0.49
Number of analog inputs2
Number of analog inputs NoteThe differential analog inputs can be configured as supplementary digital inputs
Number of analog outputs2
Number of digital inputs6
Number of digital inputs NoteOptically isolated, free reference potential (own potential group), NPN/PNP-logic selectable via wiring
Number of digital inputs with fail-safe1
Number of digital inputs with fail-safe NoteUse of 2 × DI Standard
Number of digital outputs as relay change-over contact2
Ambient temperature during operation maximum [°C]55
Number of digital outputs as transistor1
Number of interfaces acc. to 20 mA (TTY)4
Number of interfaces acc. to Industrial Ethernet2
Number of interfaces acc. to PROFINET2
Number of interfaces acc. to RS 2321
Number of interfaces acc. to RS 4220
Number of interfaces acc. to RS 4850
Number of interfaces acc. to USB1
Number of interfaces parallel0
Operating voltage from external supply voltage maximum [V]28.8
Ambient temperature during operation minimum [°C]-10
Operating voltage from external supply voltage minimum [V]20.4
Operating voltage from power module [V]24
Output current at analog output when selecting operating mode: current mode [mA]20
Output current of digital outputs as relay change-over contact with resistive load at DC [A]0.5
Output current of digital outputs as transistor with resistive load at DC [A]0.5
Output voltage at analog output when selecting operating mode: voltage mode [V]10
Output voltage at the digital outputs as relay change-over contact with resistive load at DC [V]30
Output voltage of digital outputs as transistor with resistive load at DC [V]30
Power loss [W] maximum [W]5.5
product brandnameSinamics
Ambient temperature during storage maximum [°C]70
Product component optical interfaceNo
Product component PC interfaceYes
Product designationCU240E-2 PN
Product function for U/f control ECO mode linear or quadraticYes
Product function for U/f control flux current controlYes
Product function for U/f control linear or quadratic parameterizationYes
Product function Torque control with encoderNo
Product function Torque control without encoderYes
Product function vector control with encoderNo
Product function vector control without encoderYes
Ambient temperature during storage minimum [°C]-40
Product type designationG120
Protection class IPIP20
Protection function of analog input Overvoltage protectionYes
Protection function of analog input Overvoltage protection NoteAnalog inputs are protected against inputs in a voltage range of ±30 V and have a common mode voltage in the range of ±15 V
Protection function of analog outputs Short-circuit protectionYes
Protocol for bus system for integrated interfacePROFIdrive Profile V4.1
Protocol is supported AS-interface protocolNo
Protocol is supported ASIsafe (Safety at work) protocolNo
Protocol is supported CAN protocolNo
Protocol is supported data highway protocolNo
Ambient temperature [°F] during operation maximum [°F]131
Protocol is supported DeviceNet protocolNo
Protocol is supported DeviceNet safety protocolNo
Protocol is supported EIB/KNX protocolNo
Protocol is supported EtherNet/IP protocolYes
Protocol is supported Foundation Fieldbus protocolNo
Protocol is supported INTERBus protocolNo
Protocol is supported INTERBus safety protocolNo
Protocol is supported LON protocolNo
Protocol is supported MODBus protocolNo
Protocol is supported other protocolsNo

Delivery Information

Export Control RegulationsAL : 9I999KP / ECCN : N
Standard lead time ex-works10 Day/Days
Net Weight (lb)1.08 lb
Product Dimensions (W x L x H)Not available
Packaging Dimension3.661 x 9.449 x 2.677
Package size unit of measurein
Quantity Unit1 Piece
Packaging Quantity1

Additional Product Information

EAN4042948661864
UPC40892941999
Commodity Code85049099
LKZ_FDB/ CatalogIDD11.1SD
Product Group9779
Country of originGreat Britain
RoHS ComplianceSince: 07/01/2006
ReturnableYes
Obligation Category for taking back electrical and electronic equipment after useNo obligation to take back electrical and electronic equipment after use