I/O module - AXL F AI4 I 1H - 2688491

Produttore:
PHOENIX CONTACT
Phoenix%20contact

01d84ead765b4e9e38f11701090dc446105df82f medium
Prezzo (IVA esclusa)
€ 391.10
Codice Nuova Elva
2688491
Codice produttore
2688491
Disponibilità
Invia RdO

Axioline F, Analog input module, Analog inputs: 4, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection method: 2, 3, 4-wire, transmission speed in the local bus: 100 Mbps, integrated sensor supply, degree of protection: IP20, including bus base module and Axioline F connectors

Features

  • 4 analog, bipolar input channels for the connection of current signals

  • Connection of sensors in 2, 3, and 4-wire technology

  • Current ranges: 0 mA ... 20 mA, 4 mA ... 20 mA, ±20 mA

  • Simultaneous scanning of all channels by means of simultaneous sampling

  • High crosstalk attenuation between the channels, thanks to separate signal paths

  • Particularly robust against electromagnetic interference

  • Device rating plate stored

  • BV

  • BSH

  • cULus Listed

  • EAC

  • LR

  • RINA

  • PRS

  • DNV GL

  • KR

  • ABS

  • UL Listed

  • cUL Listed

Specifications

Depth54 mm
Height126.1 mm
Strip Length8 mm
Width35 mm

Electrical isolation

Test section5 V supply of the local bus (UBus) / 24 V supply (I/Os) 500 V AC 50 Hz 1 min.
Test section5 V supply (logic)/analog inputs 500 V AC 50 Hz 1 min.
Test section5 V supply of the local bus (UBus) / functional ground 500 V AC 50 Hz 1 min.
Test section24 V supply (I/O)/analog inputs 500 V AC 50 Hz 1 min.
Test section24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min.
Test sectionAnalog inputs/functional earth ground 500 V AC 50 Hz 1 min.

Environmental Product Compliance

REACh SVHCLead 7439-92-1
China RoHSEnvironmentally Friendly Use Period = 50 years
China RoHSFor details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

Connection data

DesignationAxioline F connector
Connection methodPush-in connection
Note on the connection methodPlease observe the information provided on conductor cross sections in the 'Axioline F: system and installation' user manual.
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.1.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.1.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.16
Stripping length8 mm

Axioline potentials

DesignationAxioline F local bus supply (UBus)
Supply voltage5 V DC (via bus base module)
Current consumptiontyp. 120 mA
Current consumptionmax. 150 mA
DesignationSupply for analog modules (UA)
Supply voltage24 V DC (I/O supply and sensor supply)
Supply voltage range19.2 V DC - 30 V DC (including all tolerances, including ripple)
Current consumptionmax. 45 mA (IiS = 0 mA)
Current consumptiontyp. 118 mA (IiS = 4 x 20 mA (nominal load))
Current consumptionmax. 125 mA (IiS = 4 x 20 mA (nominal load))
Current consumptiontyp. 238 mA (IiS = 4 x 50 mA (full load))
Current consumptionmax. 245 mA (IiS = 4 x 50 mA (full load))
Power consumptiontyp. 1.5 W (at UBus and UA)
Power consumptionmax. 1.83 W (at UBus and UA)
Protective circuitSurge protection of the supply voltage electronic (35 V, 0.5 s)
Protective circuitPolarity reversal protection of the supply voltage up to HW 02: polarity protection diodeas of HW 03: parallel diode; with external 5 A fuse (for startup only)
Protective circuitTransient protection supply voltage Suppressor diode

Dimensions

Width35 mm
Height126.1 mm
Depth54 mm
Note on dimensionsThe depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715).

Interfaces

DesignationAxioline F local bus
No. of channels2
Connection methodBus base module
Transmission speed100 Mbps

Analog inputs

Description of the inputDifferential inputs, current
Input nameAnalog inputs
Number of inputs4
Connection methodPush-in connection
Connection technology2, 3, 4-wire
Note regarding the connection technologyshielded
A/D conversion time31.25 µs
A/D converter resolution16 bit
Limit frequency (3 dB)30 Hz
Limit frequency (3 dB)12 kHz
Type of protectionTransient protection of inputs
Type of protectionOverload protection of the inputs
Data formatsIB IL, S7-compatible
Measured value representation16 bits (15 bits + sign bit)
Current input signal0 mA - 20 mA
Current input signal4 mA - 20 mA
Current input signal-20 mA - 20 mA
Input resistance current input104 Ω (typical)
Input filter30 Hz, 12 kHz and mean-value generation (can be parameterized)

Ambient conditions

Air pressure (operation)70 kPa - 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa - 106 kPa (up to 3000 m above sea level)
Degree of protectionIP20
Ambient temperature (operation)-25 °C - 60 °C
Ambient temperature (storage/transport)-40 °C - 85 °C
Permissible humidity (operation)5 % - 95 % (non-condensing)
Permissible humidity (storage/transport)5 % - 95 % (non-condensing)

Standards and Regulations

Mechanical testsVibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
Mechanical testsShock in acc. with EN 60068-2-27/IEC 60068-2-27 30g
Mechanical testsContinuous shock according to EN 60068-2-27/IEC 60068-2-27 10g
Protection classIII (IEC 61140, EN 61140, VDE 0140-1)

Spesso acquistati assieme


Altri articoli da PHOENIX CONTACT

Richiedi un preventivo