SACE EMAX MOVING PART FOR CIRCUIT-BREAKER E6H 6300A THRE-POLE OVERCURRENT RELEASE PR122/P-LSI R6300 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
Specifications
Ordering | |
---|---|
Minimum Order Quantity | 1 piece |
Customs Tariff Number | 85362090 |
Dimensions | |
Product Net Width | 810 mm |
Product Net Height | 461 mm |
Product Net Depth / Length | 396.5 mm |
Product Net Weight | 116 kg |
Container Information | |
Package Level 1 Gross Weight | 138 kg |
Package Level 1 EAN | 8015644583682 |
Package Level 1 Units | 1 piece |
Package Level 1 Width | 515 mm |
Package Level 1 Height | 600 mm |
Package Level 1 Depth / Length | 1000 mm |
Additional Information | |
Current Type | AC |
Electrical Durability | Ue =< 440 V 2000 cycleUe = 500 ... 690 V 1500 cycle10 cycles per hour |
Mechanical Durability | 12000 cycle60 cycles per hour |
Number of Poles | 3 |
Power Loss | 1100 W |
Product Main Type | SACE Emax |
Product Name | Air Circuit Breaker |
Product Type | Air Circuit Breaker |
Rated Current (In) | 6300 A |
Rated Voltage (Ur) | 690 V |
Rated Impulse Withstand Voltage (Uimp) | 12 kV |
Rated Insulation Voltage (Ui) | 1000 V |
Rated Operational Current (Ie) | 6300 A |
Rated Operational Voltage | 690 V AC |
Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 100 kA(230 V AC) 100 kA(380 V AC) 100 kA(400 V AC) 100 kA(415 V AC) 100 kA(440 V AC) 100 kA(500 V AC) 100 kA(660 V AC) 100 kA(690 V AC) 100 kA |
Rated Short-time Withstand Current (Icw) | for 1 s 100 kAfor 3 s 85 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 100 kA(230 V AC) 100 kA(380 V AC) 100 kA(400 V AC) 100 kA(415 V AC) 100 kA(440 V AC) 100 kA(500 V AC) 100 kA(660 V AC) 100 kA(690 V AC) 100 kA |
Rated Uninterrupted Current (Iu) | 6300 A |
Release | PR122/P-LSI |
Release Type | EL |
Short-Circuit Performance Level | H |
Standards | IEC |
Sub-type | E6 |
Terminal Connection Type | Withdrawable Circuit-Breakers |
Version | W |
Classifications | |
ETIM 4 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
ETIM 5 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
Object Classification Code | Q |
WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) |