T5S 400 PR221DS-LS/I In=400 3p F F

Produttore:
ABB
Abb

4ed27fc0dce711c1334cee3e0ee2e89d2e1aed0d medium
Prezzo (IVA esclusa)
€ 2380.50
Codice Nuova Elva
1SDA054333R1
Codice produttore
1SDA054333R1
Disponibilità
Tempo di consegna standard: 5 giorni

C.BREAKER TMAX T5S 400 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC PR221DS-LS/I R 400

Specifications

Ordering

E-Number (Finland)3655325
E-Number (Sweden)3180383
Minimum Order Quantity1 piece
Customs Tariff Number85362090

Dimensions

Product Net Width140 mm
Product Net Height205 mm
Product Net Depth / Length103.5 mm
Product Net Weight4.824 kg

Container Information

Package Level 1 Height240 mm
Package Level 1 Depth / Length285 mm
Package Level 1 Gross Weight5.1 kg
Package Level 1 EAN8015644554316
Package Level 1 Units1 piece
Package Level 1 Width248 mm

Additional Information

Electrical Durability7000 cycle60 cycles per hour
Mechanical Durability20000 cycle120 cycles per hour
Number of Poles3
Power Lossat Rated Operating Conditions per Pole 16.5 W
Product Main TypeSACE Tmax T
Product NameMoulded Case Circuit Breaker
Product TypeCB
Rated Current (In)Main Circuit 400 A
Rated Impulse Withstand Voltage (Uimp)8 kV
Rated Insulation Voltage (Ui)1000 V
Rated Operational Voltage690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)(220 V AC) 85 kA(230 V AC) 85 kA(380 V AC) 50 kA(400 V AC) 50 kA(415 V AC) 50 kA(440 V AC) 40 kA(500 V AC) 30 kA(690 V AC) 25 kA
Rated Short-time Withstand Current (Icw)for 1 s 5 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(220 V AC) 85 kA(230 V AC) 85 kA(380 V AC) 50 kA(400 V AC) 50 kA(415 V AC) 50 kA(440 V AC) 40 kA(500 V AC) 30 kA(690 V AC) 25 kA
Rated Uninterrupted Current (Iu)400 A
ReleasePR221DS-LS/I
Release TypeEL
Short-Circuit Performance LevelS
StandardsIEC
Sub-typeT5
Suitable ForT5
Suitable for Product ClassMoulded Case Circuit Breakers
Terminal Connection TypeFixed Circuit-BreakersFront
Test Voltage Max (Utest)3500 V
Test Voltage at Industrial Frequency for 1 Minute3500 V
VersionF

Classifications

ETIM 4EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 5EC000228 - Power circuit-breaker for trafo/generator/installation prot.
Object Classification CodeQ
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)

Altri articoli da ABB

Richiedi un preventivo