MS116-10 Manual Motor Starter

Produttore:
ABB
Abb

374a5048430967c6908d1567dc12199330402308 medium
Prezzo (IVA esclusa)
€ 70.85
Codice Nuova Elva
1SAM250000R1010
Codice produttore
1SAM250000R1010
Disponibilità
Tempo di consegna standard: 5 giorni

The MS116-10 manual motor starter (also known as motor protection circuit breaker or manual motor protector) is a compact 45 mm width device with a rated operational current of Ie = 10.0 A. This device is used to manually switch on and off motors and to protect them reliably and without the need for a fuse from short-circuits, overload and phase failures. The manual motor starter offers a rated service short-circuit breaking capacity Ics = 50 kA at 400 VAC and trip class 10A.

Specifications

Ordering

Minimum Order Quantity1 piece
Customs Tariff Number85362010

Dimensions

Product Net Width45 mm
Product Net Height90 mm
Product Net Depth / Length85.6 mm
Product Net Weight0.265 kg

Technical

Rated Operational Power AC-3 (Pe)(400 V) Three Phase 4 kW
Rated Operational Power AC-3e (Pe)(400 V) Three Phase 4 kW
Rated Operational VoltageMain Circuit 690 V AC
Rated Operational Current (Ie)10 A
Rated Operational Current AC-3 (Ie)10 A
Rated Operational Current AC-3e (Ie)10 A
Rated Frequency (f)Main Circuit 50 HzMain Circuit 60 Hz
Rated Impulse Withstand Voltage (Uimp)Main Circuit 6 kV
Rated Insulation Voltage (Ui)690 V
Power Lossat Rated Operating Conditions per Pole 0.9 W
Number of Poles3
Conventional Free-air Thermal Current (Ith)Main Circuit 10 A
Degree of ProtectionHousing IP20Main Circuit Terminals IP10
Pollution Degree3
Electrical Durability100000 cycle
Mechanical Durability100000 cycle
Terminal TypeScrew Terminals
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm²Flexible 1/2x 0.75 ... 2.5 mm²Rigid 1/2x 1 ... 4 mm²
Tightening TorqueMain Circuit 0.8 ... 1.2 N·m
Wire Stripping LengthMain Circuit 9 mm
Recommended Screw DriverPozidriv 2
Mounting PositionPosition 1 to 6
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Minimum Mounting DistanceElectrical Conductive Board, Horizontal - Up to 400 V 0 mmElectrical Conductive Board, Horizontal - Up to 690 V 1.5 mmElectrical Conductive Board, Vertical 75 mmOther Device Same Type, Horizontal 0 mmOther Device Same Type, Vertical 150 mm
Actuator TypeRotary Handle
Contact Position IndicationON / OFF
StandardsIEC/EN 60947-1IEC/EN 60947-2IEC/EN 60947-4-1UL 60947-1UL 60947-4-1
Rated Service Short-Circuit Breaking Capacity (Ics)(230 V AC) 50 kA(400 V AC) 50 kA(440 V AC) 6 kA(500 V AC) 6 kA(690 V AC) 2 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(230 V AC) 50 kA(400 V AC) 50 kA(440 V AC) 18 kA(500 V AC) 10 kA(690 V AC) 3 kA
Rated Instantaneous Short-Circuit Current Setting (Ii)150 A
Setting Range6.3 ... 10 A

Technical UL/CSA

Short-Circuit Current Rating (SCCR)Any UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 18 kAAny UL Listed Fuses or Circuit-Breakers, Group Installations (600 V AC) 5 kAAny UL Listed Fuses or Circuit-Breakers, Motor Disconnect (480 V AC) 18 kAAny UL Listed Fuses or Circuit-Breakers, Motor Disconnect (600 V AC) 5 kA
Maximum Operating Voltage UL/CSAMain Circuit 600 V AC
Ampere Rating UL/CSA10 A
Horsepower Rating UL/CSA(200 V AC) Three Phase 2 Hp(208 V AC) Three Phase 2 Hp(220 ... 240 V AC) Three Phase 3 Hp(440 ... 480 V AC) Three Phase 5 Hp(550 ... 600 V AC) Three Phase 7.5 Hp
Full Load Amps Motor Use(200 V AC) Three Phase 7.8 A(208 V AC) Three Phase 7.5 A(220 ... 240 V AC) Three Phase 9.6 A(440 ... 480 V AC) Three Phase 7.6 A(550 ... 600 V AC) Three Phase 9 A
Locked Rotor Amps(200 V AC) Three Phase 57.5 A(208 V AC) Three Phase 55 A(220 ... 240 V AC) Three Phase 64 A(440 ... 480 V AC) Three Phase 46 A(550 ... 600 V AC) Three Phase 50.8 A
General Use Rating UL/CSA(600 V AC) 10 A
Connecting Capacity Main Circuit UL/CSAFlexible 1/2x 16-12 AWGStranded 1/2x 16-12 AWG
Tightening Torque UL/CSAMain Circuit 10 in·lb

Environmental

Ambient Air TemperatureAround the Enclosure 0 ... +40 °COperation -25 ... +70 °COperation Compensated -25 ... +55 °CStorage -50 ... +80 °C
Ambient Air Temperature CompensationYes
Maximum Operating Altitude Permissible2000 m
Resistance to Shock acc. to IEC 60068-2-2711 ms Pulse 25g
Resistance to Vibrations acc. to IEC 60068-2-65g / 3 ... 150 Hz
RoHS StatusFollowing EU Directive 2011/65/EU

Container Information

Package Level 1 Unitsbox 1 piece
Package Level 1 Width92 mm
Package Level 1 Depth / Length95 mm
Package Level 1 Height50 mm
Package Level 1 Gross Weight0.28 kg
Package Level 1 EAN4013614320330
Package Level 2 Unitscarton 40 piece
Package Level 2 Width280 mm
Package Level 2 Depth / Length395 mm
Package Level 2 Height210 mm
Package Level 2 Gross Weight11.586 kg
Package Level 2 EAN4013614408700

Classifications

Object Classification CodeF
ETIM 4EC000074 - Motor protective circuit-breaker
ETIM 5EC000074 - Motor protective circuit-breaker
eClassV11.0 : 27370401
IDEA Granular Category Code (IGCC)4845 >> 3 Pole Motor Circuit Protector Circuit Breakers
E-Number (Finland)3706010
E-Number (Sweden)3111948

Altri articoli da ABB

Richiedi un preventivo