XT4S 250 TMA 250-2500 3p F F

Manufactured by:
ABB
Abb

61b9bdfe0b236835f4c5c3cc685350ebaebab83b medium
Nuova Elva code
XT4S250TMA3
Manufacturer code
1SDA068312R1
Availability
Send request for quotation

C.BREAKER TMAX XT4S 250 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 250 I3=1250...2500 A

Specifications

Ordering

E-Number (Finland)3638192
Minimum Order Quantity1 piece
Customs Tariff Number85362090

Dimensions

Product Net Width105 mm
Product Net Height160 mm
Product Net Depth / Length82.5 mm
Product Net Weight2.254 kg

Container Information

Package Level 1 Depth / Length168 mm
Package Level 1 Gross Weight2.373 kg
Package Level 1 EAN8015644022181
Package Level 1 Units1 piece
Package Level 1 Width145 mm
Package Level 1 Height210 mm

Environmental

RoHS StatusFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Additional Information

Circuit Breaker Type to be AssociatedPower Distribution
Current TypeAC/DC
Electrical Durability120 cycles per hour8000 cycle
Mechanical DurabilityNr. Operations 240 cycles per hourNr. Operations 25000 cycle
Number of Poles3
Opening TimeCB with SOR 15 msCB with UVR 15 ms
Order Multiple1 piece
Power Lossat Rated Operating Conditions per Pole 16.44 W
Product Main TypeSACE Tmax XT
Product NameMoulded Case Circuit Breaker
Product TypeCB
Rated Current (In)250 A
Rated Frequency (f)50 / 60 Hz
Rated Voltage (Ur)690 V
Rated Impulse Withstand Voltage (Uimp)8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)1250…2500 A
Rated Insulation Voltage (Ui)1000 V
Rated Operational Voltage690 V AC500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)(220 V AC) 85 kA(230 V AC) 85 kA(240 V AC) 85 kA(380 V AC) 50 kA(415 V AC) 50 kA(440 V AC) 50 kA(500 V AC) 36 kA(525 V AC) 25 kA(690 V AC) 12 kA(250 V DC) 2 Poles in Series 50 kA(500 V DC) 2 Poles in Series 50 kA(500 V DC) 3 Poles in Series 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(220 V AC) 85 kA(230 V AC) 85 kA(240 V AC) 85 kA(380 V AC) 50 kA(415 V AC) 50 kA(440 V AC) 50 kA(500 V AC) 36 kA(525 V AC) 25 kA(690 V AC) 12 kA(250 V DC) 2 Poles in Series 50 kA(500 V DC) 2 Poles in Series 50 kA(500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)250 A
ReleaseTMA
Release TypeTM
Setting Range175...250 A
Short-Circuit Performance LevelS
StandardsIEC
Sub-typeXT4
Terminal Connection TypeFixed Circuit-Breakers
VersionF

Classifications

ETIM 4EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 5EC000228 - Power circuit-breaker for trafo/generator/installation prot.
Object Classification CodeQ
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)

Other ABB items