XT4S 250 TMA 200-2000 4p F F InN=100%

Manufactured by:
ABB
Abb

Ce077efd8628d996ddb7cf78f5d8e53fc782abe4 medium
Nuova Elva code
XT4S200TMAN
Manufacturer code
1SDA068329R1
Availability
Send request for quotation

C.BREAKER TMAX XT4S 250 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 200 I3=1000...2000 A FULLY RATED NEUTRAL

Specifications

Ordering

Minimum Order Quantity1 piece
Customs Tariff Number85362090

Dimensions

Product Net Width140 mm
Product Net Height160 mm
Product Net Depth / Length82.5 mm
Product Net Weight3.05 kg

Container Information

Package Level 1 Gross Weight3.5 kg
Package Level 1 EAN8015644696375
Package Level 1 Units1 piece
Package Level 1 Width145 mm
Package Level 1 Height210 mm
Package Level 1 Depth / Length168 mm

Environmental

RoHS StatusFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Additional Information

Circuit Breaker Type to be AssociatedPower Distribution
Current TypeAC/DC
Electrical Durability120 cycles per hour8000 cycle
Mechanical DurabilityNr. Operations 240 cycles per hourNr. Operations 25000 cycle
Number of Poles4
Opening TimeCB with SOR 15 msCB with UVR 15 ms
Order Multiple1 piece
Power Lossat Rated Operating Conditions per Pole 11.88 W
Product Main TypeSACE Tmax XT
Product NameMoulded Case Circuit Breaker
Product TypeCB
Rated Current (In)200 A
Rated Frequency (f)50 / 60 Hz
Rated Voltage (Ur)690 V
Rated Impulse Withstand Voltage (Uimp)8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)1000…2000 A
Rated Insulation Voltage (Ui)1000 V
Rated Operational Voltage690 V AC500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)(220 V AC) 85 kA(230 V AC) 85 kA(240 V AC) 85 kA(380 V AC) 50 kA(415 V AC) 50 kA(440 V AC) 50 kA(500 V AC) 36 kA(525 V AC) 25 kA(690 V AC) 12 kA(250 V DC) 2 Poles in Series 50 kA(500 V DC) 2 Poles in Series 50 kA(500 V DC) 3 Poles in Series 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(220 V AC) 85 kA(230 V AC) 85 kA(240 V AC) 85 kA(380 V AC) 50 kA(415 V AC) 50 kA(440 V AC) 50 kA(500 V AC) 36 kA(525 V AC) 25 kA(690 V AC) 12 kA(250 V DC) 2 Poles in Series 50 kA(500 V DC) 2 Poles in Series 50 kA(500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)250 A
ReleaseTMA
Release TypeTM
Setting Range140...200 A
Short-Circuit Performance LevelS
StandardsIEC
Sub-typeXT4
Terminal Connection TypeFixed Circuit-Breakers
VersionF

Classifications

ETIM 4EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 5EC000228 - Power circuit-breaker for trafo/generator/installation prot.
Object Classification CodeQ
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)